Calculate the reverberation time of an open-plan office

Room

Room use
Dimensions
Volume720 m³Floor area240 m²Wall area192 m²
Surfaces
Floor
Walls
Ceiling
Furnishings

Nothing added yet.

An empty room reverberates the most. Add people, furniture or windows for a realistic picture.

Current state1.53s
With measuresNo measures yet
0.93 s above targetToo reverberant. Add absorbers.
Reverberation time by frequency
Terms of use

Measures

No measures yet

Add acoustic products and see the effect instantly.

In an open-plan office the acoustics decide over concentration and speech intelligibility. ASR A3.7 sets a maximum, DIN 18041 a minimum absorption, ISO 22955 describes office types. The calculator starts with 720 m³ (Multi-person or open-plan office), target value at most 0.60 s, and shows how much ceiling or how many screens from 2,004 products with measured data are needed.

Target values by standard

Target values for an open-plan office in three room sizes. Reverberation time is only part of the assessment; ISO 22955 and VDI 2569 also rate the level decay over distance.

StandardUse300 m³700 m³1,500 m³
ASR A3.7, workplacesASR A3.7:2021-03Multi-person or open-plan officeat most 0.60 sat most 0.60 sat most 0.60 s
ÖNORM B 8115-3ÖNORM B 8115-3:2023-07Multi-person office (Klasse B)at most 0.55 sat most 0.55 sat most 0.55 s
SECO guide to ArGV 3, art. 22SECO-Wegleitung ArGV 3, Art. 22 (2021)Multi-person or open-plan office (Gruppe 2/3)at most 0.71 sat most 0.71 sat most 0.71 s
NF S 31-080, officesNF S 31-080:2006Open-plan office (performant)at most 1.00 sat most 1.00 sat most 1.00 s
SS 25268, offices (Sweden)SS 25268:2023Open-plan office (5 or more workstations)at most 0.40 sat most 0.40 sat most 0.40 s
SFS 5907, classes A1 and A2 (Finland)SFS 5907:2022Open-plan office, furnished (A2)at most 0.40 sat most 0.40 sat most 0.40 s
PN-B-02151-4, reverberation and speech intelligibility (Poland)PN-B-02151-4:2015-06Open-plan office, bank hall, customer service (A ≥ 1,1 S)at most 0.44 sat most 0.44 sat most 0.44 s
LEED v4, acoustic performanceLEED v4 / v4.1 EQ Credit: Acoustic PerformanceOpen-plan office (with or without sound masking)at most 0.80 sat most 0.80 sat most 0.80 s
ISO 22955, open-plan officesISO 22955:2021Mostly individual work (accounting, engineering, programming) (Typ 4)at most 0.50 sat most 0.50 sat most 0.50 s

Typical measures

  • Full-area class A acoustic ceiling: the only surface that works everywhere.
  • Ceiling rafts or baffles above team zones when the ceiling is occupied.
  • Upholstered screens and cabinet walls between the zones.
  • Carpet and soft furniture lower the level, but do not replace zoning.

Frequently asked questions

What reverberation time applies in an open-plan office?

Under ASR A3.7 at most 0.6 s, averaged over 500 and 1,000 Hz. For room group B4 DIN 18041 requires a minimum absorption of A/V from 0.25 m⁻¹ at room heights up to 2.5 m.

Why is reverberation time not enough as a criterion?

Because in an open plan the sound from the neighbouring zone disturbs, not the reverberation of the whole room. VDI 2569 and ISO 22955 therefore also rate the level decay with distance.

How many ceiling rafts does an open-plan office need?

Without a continuous acoustic ceiling, around 60 to 80 percent of the floor area in class A absorbers. The calculator names the quantity per product from the measured curve.

Other room types

Formulas, DIN 18041 and worked example on the calculator page