Mineral woolHighly absorbent
Data source
PTB reference data
Physikalisch-Technische Bundesanstalt
Source: C.M.Harris, Noise Control in Buildings, McGraw Hill 1994
Value from the PTB table, not verified
Manville Micro-Aire Type 475 FSK coated duct board
Type 475 FSK – Micro-Aire
PTB reference data
Original description
Manville Micro-Aire Type 475 FSK coated duct board
Material properties
Manufacturer: Manville
Thickness: 1 inch, 1 1/2 inch
Wall distance: 0 in, 1 in
Measurement data
Sound absorption
Reverberation chamber (ASTM C423 / ISO 354)· 6 variants
NRC
0.95
Frequency values
αp per octave band
| f (Hz) | 125 | 250 | 500 | 1k | 2k | 4k |
|---|---|---|---|---|---|---|
| αp | 0.45 | 0.60 | 0.95 | 1.00 | 1.00 | 1.00 |
Create a permanent free account — Access frequency bands, variants and export.
Free. No password required.
| Compare | Value | |||
|---|---|---|---|---|
| 1 1/2 inch | 0.47 lb/ft² | 1 in | NRC0.95 | |
| 1 1/2 inch | 0.47 lb/ft² | 0 | NRC0.90 | |
| 1 inch | 0.42 lb/ft² | 1 in | NRC0.80 | |
| 1 inch | 0.35 lb/ft² | 1 in | NRC0.70 | |
| 1 inch | 0.42 lb/ft² | 0 | NRC0.75 | |
| 1 inch | 0.35 lb/ft² | 0 | NRC0.65 |
NRC: 0.95 (derived from ISO 354 lab data)
Dimensions: to 48 x 120 inches
Measured values as a table (6 measurements)
| Build-up | NRC | 125 Hz | 250 Hz | 500 Hz | 1000 Hz | 2000 Hz | 4000 Hz |
|---|---|---|---|---|---|---|---|
| 1 inch · 0.35 lb/ft² · 0 | 0.65 | 0.06 | 0.22 | 0.61 | 0.86 | 1.00 | 1.04 |
| 1 inch · 0.42 lb/ft² · 0 | 0.75 | 0.01 | 0.23 | 0.67 | 0.98 | 1.05 | 1.06 |
| 1 1/2 inch · 0.47 lb/ft² · 0 | 0.90 | 0.11 | 0.45 | 0.99 | 1.11 | 1.09 | 1.07 |
| 1 inch · 0.35 lb/ft² · 25 mm | 0.70 | 0.46 | 0.30 | 0.58 | 0.85 | 1.00 | 1.03 |
| 1 inch · 0.42 lb/ft² · 25 mm | 0.80 | 0.29 | 0.42 | 0.70 | 1.00 | 1.06 | 1.08 |
| 1 1/2 inch · 0.47 lb/ft² · 25 mm | 0.95 | 0.46 | 0.58 | 0.95 | 1.10 | 1.08 | 1.09 |
Measured values as a table (6 measurements)
Access frequency bands, variants and export. Create a permanent free account
Last updated: