Mineral woolHighly absorbent

Data source

PTB reference data

Physikalisch-Technische Bundesanstalt

Source: C.M.Harris, Noise Control in Buildings, McGraw Hill 1994

Value from the PTB table, not verified

Manville Linacoustic Permacote duct liner, spacing 0 mm

Linacoustic

PTB reference data

Original description

Manville Linacoustic Permacote duct liner, spacing 0 mm

Material properties

Manufacturer: Manville
Thickness: 1 inch
Wall distance: 0 in

Measurement data

Sound absorption

Reverberation chamber (ASTM C423 / ISO 354)

NRC
0.75
derived from ISO 354 lab data

Frequency values

αp nach ISO 11654

f (Hz)1252505001k2k4k
αp0.100.300.700.901.001.00

Create a permanent free accountAccess frequency bands, variants and export.

Free. No password required.

Value from the PTB table, not verified

NRC: 0.75 (derived from ISO 354 lab data)

Terms of use
Measured values as a table (1 measurement)
Manville Linacoustic Permacote duct liner, spacing 0 mm: sound absorption coefficient αs per ISO 354 by frequency and test build-up
Build-upNRC125 Hz250 Hz500 Hz1000 Hz2000 Hz4000 Hz
1 inch · 0.18 lb/ft² · 00.750.090.310.690.911.021.03
Measured values as a table (1 measurement)