Manufacturer
Lindner Group
Lindner Group, Arnstorf: metal ceilings, heating and cooling ceilings, raised floors, wall and ceiling linings and the MUTE+ sound absorber line.
Documents
Plafotherm GK HEKDA
Description
Plasterboard heating and cooling ceiling with a heat conducting profile as a fine grid. The perforation pattern and the centre spacing of the heat conducting profile determine the absorption. Nominal cooling capacity 81.70 to 99.60 W/m² at 10 K per EN 14240, nominal heating capacity 102 to 108 W/m² at 15 K per EN 14037:2003, depending on the board type and edge configuration and referred to the active area.
Technical data
Measurement data
Sound absorption
Reverberation chamber (ASTM C423 / ISO 354)· 8 variants
Frequency values
αp per octave band
| f (Hz) | 125 | 250 | 500 | 1k | 2k | 4k |
|---|---|---|---|---|---|---|
| αp | 0.55 | 0.60 | 0.55 | 0.45 | 0.40 | 0.55 |
Create a permanent free account — Access frequency bands, variants and export.
Free. No password required.
| Compare | Value | |
|---|---|---|
| 12-25 Q | NRC0.50 | |
| 8/18 Q | NRC0.45 | |
| 8-18 R | NRC0.35 | |
| 12-25 R | NRC0.45 | |
| 8-18 Q | NRC0.35 | |
| 12-25 R | NRC0.30 | |
| 12-25 Q | NRC0.30 | |
| 8-18 R | NRC0.20 |
Test report: H180228/A_rev00 (Messung H180228/A7a_rev00)
NRC: 0.50 (derived from ISO 354 lab data)
Measurement date: 2018-03-06
Distance: 7.9 in
Measured values as a table (8 measurements)
| Build-up | NRC | 100 Hz | 125 Hz | 160 Hz | 200 Hz | 250 Hz | 315 Hz | 400 Hz | 500 Hz | 630 Hz | 800 Hz | 1000 Hz | 1250 Hz | 1600 Hz | 2000 Hz | 2500 Hz | 3150 Hz | 4000 Hz | 5000 Hz |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 8-18 R · 200 mm · axis spacing 260 mm, with heat-conducting profile | 0.20 | 0.25 | 0.19 | 0.31 | 0.28 | 0.21 | 0.25 | 0.22 | 0.23 | 0.19 | 0.19 | 0.20 | 0.20 | 0.19 | 0.23 | 0.28 | 0.34 | 0.51 | 0.82 |
| 12-25 R · 200 mm · axis spacing 260 mm, with heat-conducting profile | 0.30 | 0.42 | 0.43 | 0.46 | 0.39 | 0.40 | 0.41 | 0.32 | 0.35 | 0.29 | 0.27 | 0.24 | 0.25 | 0.23 | 0.23 | 0.28 | 0.36 | 0.56 | 0.81 |
| 8-18 R · 200 mm · axis spacing 333 mm, with heat-conducting profile | 0.35 | 0.34 | 0.26 | 0.45 | 0.44 | 0.38 | 0.42 | 0.39 | 0.37 | 0.37 | 0.34 | 0.34 | 0.35 | 0.35 | 0.36 | 0.39 | 0.45 | 0.57 | 0.79 |
| 12-25 Q · 200 mm · axis spacing 260 mm, with heat-conducting profile | 0.30 | 0.38 | 0.51 | 0.45 | 0.36 | 0.38 | 0.39 | 0.33 | 0.32 | 0.29 | 0.27 | 0.25 | 0.25 | 0.25 | 0.24 | 0.29 | 0.36 | 0.54 | 0.77 |
| 8-18 Q · 200 mm · axis spacing 260 mm, with heat-conducting profile | 0.35 | 0.41 | 0.50 | 0.50 | 0.40 | 0.40 | 0.41 | 0.33 | 0.35 | 0.30 | 0.29 | 0.28 | 0.27 | 0.27 | 0.29 | 0.34 | 0.44 | 0.60 | 0.90 |
| 12-25 Q · 200 mm · axis spacing 333 mm, with heat-conducting profile | 0.50 | 0.52 | 0.55 | 0.56 | 0.55 | 0.56 | 0.65 | 0.63 | 0.58 | 0.50 | 0.45 | 0.41 | 0.43 | 0.42 | 0.37 | 0.39 | 0.41 | 0.50 | 0.71 |
| 12-25 R · 200 mm · axis spacing 333 mm, with heat-conducting profile | 0.45 | 0.52 | 0.50 | 0.57 | 0.54 | 0.50 | 0.58 | 0.54 | 0.53 | 0.45 | 0.41 | 0.38 | 0.41 | 0.37 | 0.35 | 0.38 | 0.44 | 0.56 | 0.76 |
| 8/18 Q · 200 mm · fine-grid heat-conducting profile, axis spacing 333 mm | 0.45 | 0.50 | 0.53 | 0.54 | 0.52 | 0.52 | 0.61 | 0.58 | 0.54 | 0.46 | 0.43 | 0.40 | 0.42 | 0.40 | 0.37 | 0.39 | 0.43 | 0.54 | 0.74 |
Measured values as a table (8 measurements)
Access frequency bands, variants and export. Create a permanent free account